Backup Battery Runtime Calculator
How much of the outage load can a backup battery cover before it reaches reserve?
Worked example
A clinic continuity exercise can estimate runtime from tested usable battery energy, steady demand and power limits. Account for reserve, conversion loss and auxiliary draw.
A fictional battery starts with 12 kWh of stored DC energy and keeps 2 kWh in reserve. At 80% conversion efficiency it supplies 8 kWh AC. A constant 3 kW load first falls short after 2 hours 40 minutes.
Try it yourself
The calculator opens with the fictional example already filled in. Change one input, choose Calculate locally, and compare the result to the original values below. Use Reset fictional fixture to start over.
An unknown result means the available inputs do not support a value. Check the calculator’s Warnings tab for what is missing or uncertain.
- AC energy delivered 8 kWh AC
- AC demand unmet 4 kWh AC
- Elapsed time to first shortfall 2.666667 hours
- Energy used by auxiliary equipment 0 kWh DC
- Remaining stored energy 2 kWh DC
Import local JSON or CSV
Files stay in this browser. Maximum 1 MiB. JSON imports are recalculated. CSV supports flat observation tables, with column types taken from the displayed fixture. Empty cells become null.
Compare the arrangements
Keep physical resources and evaluation conditions equal. With identical inputs, all three approaches produce identical arithmetic. The comparison refuses material differences in declared conditions; it does not verify those declarations.
Privacy: comparison inputs may contain sensitive notes or operational details. Storage is off by default. Do not enter personal records or sensitive infrastructure details. Reproduction exports include supplied inputs and notes, including raw small-cell inputs suppressed from CORE-009 result tables. Suppression of displayed results does not make a reproduction export safe to publish.
Executive brief and reproducible export
Review for personal, confidential or sensitive material before saving or sharing. No automatic submission occurs.
Read the generated brief
Method, inputs and limits
Account for battery energy, reserve, inverter power, auxiliary draw and load over a declared outage schedule. Method version 0.2.0. Size or certify an electrical installation, model charging, or account for startup surges, degradation or temperature.
| Input | Unit / type | Required interpretation |
|---|---|---|
| initialKwh — Initial usable battery energy | kWh DC / number | Declared stored energy at the start of the exercise. |
| reserveKwh — Energy reserved | kWh DC / number | A floor at or below the initial stored energy. |
| inverterKw — Inverter output limit | kW AC / number | Constant real power available at the AC output. |
| efficiency — Discharge conversion efficiency | fraction / number | Between 0.01 and 1. Enter 0.9 for 90%. |
| auxiliaryKw — Continuous battery-side auxiliary draw | kW DC / number | Optional controls, cooling or inverter standby draw measured at the battery. Enter zero if already included in the efficiency. |
| periods — Ordered outage intervals | hours and kW AC / number | Each row has hours and constant loadKw. No charging during the exercise. |
Visible mathematics / decision rules
Demand = load kW × interval hours.
AC power delivered while active = min(load kW, inverter output limit).
Battery draw = delivered AC power ÷ efficiency + auxiliary DC draw. Active time is capped by the energy above reserve and interval length.
Closing DC energy = opening DC energy − battery draw × active time.
What this result cannot establish
- Load, auxiliary draw and conversion efficiency are constant within each interval. Auxiliary draw stops at the reserve floor.
- A load above the inverter ceiling is short from the start of the interval. Otherwise a shortfall starts when the battery reaches reserve.
What would falsify the assumptions?
- Compare simulated interval energy and loss of load with an authorized load test at the declared reserve and efficiency.
- Assumptions fail if the supplied definitions, units, period, scope or source records are wrong or incomplete.
- An independent source audit or replication may contradict an input or the recorded dependency.
- This method creates no resources. Physical conservation is checked in the inventory and transfer ledgers; descriptive graphs and checklists are not resource-flow models.
- The same equations and review checklist can be reproduced with a spreadsheet or structured human-only process.
- This is deterministic arithmetic, a descriptive comparison or a structured governance check, not a fitted causal effect or forecast. Fictional inputs remain an exercise.
- Equal or worse measured errors, net review effort, disclosure burden or fallback under MAR would show no added benefit or added risk; no improvement is assumed.
Reproducible fictional fixture and independently calculated expectations
This fixture is synthetic. It does not describe a country, government, company or event.
{
"observations": {
"unit": "kWh",
"origin": "synthetic",
"sources": [
{
"id": "SYN-020",
"kind": "synthetic",
"label": "Fictional continuity exercise",
"url": null
}
],
"initialKwh": 12,
"reserveKwh": 2,
"inverterKw": 4,
"efficiency": 0.8,
"auxiliaryKw": 0,
"periods": [
{
"hours": 2,
"loadKw": 3
},
{
"hours": 2,
"loadKw": 3
}
]
},
"parameters": {}
}Expected checks
{
"delivered": 8,
"unmet": 4,
"firstShortfallHour": 2.666667,
"closingKwh": 2